We work with ACI, BAPI HVAC, Omega, RLE Technologies, and Veris Industries to name a few.

Temperature sensors range from normal ambient temps to extremely high temperatures to extremely low temperatures. Combination of Temperature, Humidity, and other sensing elements.

Categories are wall mount, ceiling mount, outdoor, duct, pipe/immersion, probes, button, self-adhesive surface, thermal buffer bottles, and more.

Sensor signals range from Analog 4-20mA, 0-5V, 0-10V, Thermistor (10K-2), 1K Ohm platinum RTD, Digital One-wire, Modbus, and BACnet protocol.

Our Temperature Monitoring Solutions can integrate back into an existing monitoring platform.

FMS offers stand-alone temperature monitoring for alerts and trending data depending on your needs.

Wired Temperature Monitoring

High Performance Sensors

Automation Components, Inc designs and manufactures its own line of sensors for Building Management Systems for heating, ventilation, and air conditioning – HVAC. ACI has been in business since 1991 and also offers Humidity, Pressure, Current, Gas detection, and Air Quality sensors.

Contact Us to discuss your application. ACI has a wide variety of sensors to choose from.

ACI Temperature Sensors

  • Room Mount
  • Room Mount with Display
  • Bullet Probes
  • Flush Mount
  • Duct
  • Immersion
  • Pipe Mount
  • Outdoor
  • Strap On
  • Wall Plates

 

ACI Humidity Sensors

  • Room Mount
  • Room Mount with Display
  • Duct
  • Outside Air
  • Wall Plates
  • Remote Probe

 

ACI Air Quality Sensors

From Wall Mount Room sensors with or without displays. ACI also manufactures Duct Mount style Air Quality Sensors

  • Carbon Dioxide
  • Particulate Matter
  • VOC

 

ACI Gas Detectors

From Wall Mount Room sensors with or without displays. ACI also manufactures Duct Mount style Air Quality Sensors

  • Carbon Dioxide (CO2)
  • Carbon Monoxide (CO)
  • Nitrogen Dioxide (NO2)
  • Oxygen (O2)
  • Toxic Gas
  • Combustible Gas
  • Refrigerant

 

RLE Raptor BMS-1Wire Temperature Module
FMS Integration Temperature Monitoring Icon

BMS-1WIRE

RLE Raptor Eight Input

 

RLE Raptor BMS-1WIRE

Raptor BMS-1WIRE Plug-And-Play Module

The BMS-1WIRE from RLE Technologies has eight inputs for Digital Temperature Sensors, Digital Temperature/Humidity sensors, or any combination. Designed with Temperature Integration back to Building Monitoring Systems (BMS), and Remote Monitoring Systems.

  • Serial Communications support Modbus-RTU or BACnet MS/TP
  • Temperature Sensor 1WIRE-TS
  • Temperature/Humidity Sensor 1WIRE-THS

 

Key Features

Power: Hardwired 24VDC, 500mA, or RLE power supply PSWA-DC-24-ST (optional; not included)

Included Equipment: BMS-1WIRE, DIN rail mount adapter

Required Accessories: 1-wire sensors

Wired Inputs: 8 1-wire digital temperature or 1-wire digital temperature/humidity sensor inputs; plug-and-play

Communications Ports

  • EIA-232: USB Connector; 115200 Baud, 8 data bits, no parity, 1 stop bit
  • EIA-485: 9600, 19200, 38400 or 76800 baud (selectable); Parity: None, 8 data bits 1 stop bit

Protocols

  • Modbus RTU (EIA-485): Server RTU mode, supports function codes 03 and 04
  • BACnet MS/TP (EIA-485)

External Interface

  • Push Button: Factory reset
  • LED Indicators: Power/Status – 1 tricolor; Sensor activity indicator – 1 per sensor, up to 8 total
  • DIP Switches: SW 1 – Device configuration; SW 2 – Modbus/BACnet device ID

Operating Environment

  • Temperature: 32°F to 122°F (0°C to 50°C)
  • Humidity: 5% to 95% RH, non-condensing

Dimensions: 5.25”W x 6.0”H x 1.75”D (133mmW x 152mmH x 44.5mmD)

Weight: 8.0 oz. (228g)

Mounting: Wall mount (keyhole, zip tie, or screw holes); DIN rail mount

Certifications: CE; ETL listed: conforms to UL 61010-1, IEC 61010; EN 60601-1; CSA C22.2 NO. 61010-1; IEC 55011; CISPR16; RoHS compliant.

RLE Falcon F200
FMS Integration Temperature Monitoring Icon

Falcon F200

Facility Monitoring

 

RLE Falcon F200

RLE Falcon F200

The F200 is a small form factor facility Monitoring System. It supports its own web interface for viewing and programming data, not requiring any extra third-party software. No Licensing fees or moving components, making the F200 a low maintenance device. Great for Data Closets, IDFs, MDFs, Server Cabinet Rooms, and Telecommunications Rooms.

The F200 works with up to four plug-and-play temperature and/or temperature/humidity sensors. Eight dry-contact inputs for remote equipment monitoring for alarms. A Leak Detection cable input for any of the RLE SeaHawk Sense Cables. One relay output that can be activated by any or all of the alarm inputs. Supports email notifications for alarms. Modbus TCP/IP and SNMP are available for system integration back to larger monitoring platforms.

 

  • Four Plug-And-Play sensor inputs
  • Temperature Sensor 1WIRE-TS
  • Temperature/Humidity Sensor 1WIRE-THS
  • Eight dry-contact inputs
  • One Leak Detection Input

 

F200 Product Features

  • Plug-and-play installation and setup for users
  • Hosts own web interface with a clean, easy to use, mobile-friendly
  • Eight dry contact inputs
  • Four temperature or temperature/humidity sensors
  • One zone of leak detection, Single-zone leak detection supports up to 200’ of leak detection sensing cable and/or spot detectors
  • Multiple alarm notification configurations including audible and visible indicators, integrated web interface, email messaging, and SNMP traps
  • Relay output allows for simple control of an external device upon an alarm condition
  • SNMP Protocol for Network Management System (NMS) integration
  • Modbus output enables simple integration to a Building Management System (BMS)
  • Integrated logging and trending – trending data available as a downloadable CSV file

Included Equipment: F200 controller; 5V USB (Type A) wall-wart power adapter with Type C, G, and I blades; USB mini B to USB A cable

Additional Requirements: Digital temperature sensors, digital temperature/humidity sensors, leak detection leader cable, leak detection sensing cable, SD-Z or SD-Z1 spot detectors, end-of-line terminator, network cable, rack mount kit (as needed for application)

Power: (US) 5VDC @ 500mA max; 110/240VAC 50/60Hz; Wall adapter (Type A blade) to USB connector, with Type C, G, and I blades for international use (included)

Wired Inputs

  • Temperature/Humidity: 4 1-wire digital temperature or 1-wire digital temperature/humidity sensor inputs; RJ11 connectors; plug-and-play; configurable alarm points
  • Digital (Dry Contact): 8 digital alarm points; configurable
  • Sensing Cable: One zone leak detection, compatible with all SeaHawk sensing cables and SD-Z and SD-Z1 spot detectors
    • Cable Input: Requires 15ft (4.6m) leader cable and EOL terminator (not included), or wire one SD-Z1 directly to the F200
    • Maximum Sensing Cable Length: 200ft (61m) of sensing cable

Relay Output: 1 Form C summary relay; 2A @ 30VDC, 0.5A @ 125VAC.  Configurable as summary alarm output or manual operation.

Alarm Notification

  • Panel: Audible alarm, visible LED
  • Integrated Web Interface: Dashboard overview with alarm indicators
  • Email: Up to 8 email recipients; email sent on an alarm to recipients, distribution list, or email-to-SMS
  • SNMP Traps: Multiple community strings
  • Relay: 1 Form C summary relay output

Web Interface Login Security: 8 passwords read-only users; 8 passwords read/write users

Communication Port

  • Ethernet: 10/100 BaseT, RJ45 connector; 500 VAC RMS isolation; DHCP capable; Static IP-addressable

Protocols

  • TCP/IP: ARP; DNS; UDP; DHCP
  • HTML: Supports multiple simultaneous connections
  • SMTP (email): SMTP authentication; supports SSLv3 RSA:RC4-128:MD5; up to 8 recipients
  • Modbus TCP/IP: Modbus Server; TCP/IP transmission protocol
  • SNMP: V1; V2C MIB-2 compliant; NMS Manageable with Get and Traps: V2C Get, V2C, and V1 Traps

Timekeeping: Onboard configurable real-time clock (RTC); Network Time Protocol (NTP) capable (internet access required for NTP)

Logging: Logs 50 most recent alarm and return to normal events with date/time stamp

Trending: Records up to 43,200 points of sensor data.  Sample interval set from 10 seconds to 1 day.  CSV downloadable.

Operating Environment

  • Temperature: -13° to 158°F (-25° to 70°C)
  • Humidity: 5% to 95% RH, non-condensing
  • Altitude: 15,000ft (4,572m) max.

Storage Environment: -40° to 185°F (-40° to 85°C)

Dimensions: 5.63″W x 1.00″H x 2.63″D (143mmW x 25mmH x 67mmD)

Weight: 10.1 oz. (287g)

Mounting: Standalone; keyholes included for wall mount; rack-mount bracket available

Certifications: CE; ETL listed: conforms to UL 61010-1, EN 61010-1; certified to CSA C22.2 NO. 61010-1; RoHS compliant