The Falcon F200 is a small form-factor monitoring system with all the key functions.
Ideal for IT closets, IDF, and MDF locations to help protect critical environments for businesses.
It covers the basics, Temperature Monitoring, Humidity Monitoring, Equipment alarms, and Water Leak Detection.
Environmental Monitoring for Server Rooms and IT Closets
Hosts its own webpage for viewing and configuration
Plug-and-Play Temperature Sensors
Plug-and-Play Temperature/Humidity Sensors
Dry-Contact inputs for Remote Equipment Alarms
Water Leak Detection input for RLE SeaHawk Leak Detection
Email alerts for external notification of alarms
Relay output for external notification
SNMP and Modbus TCP/IP for third-party software integration
Simple to use web interface for viewing and configuration
Using standard browsers for viewing data from the F200 inputs.
Configure the F200 from the password-protected web interface.
Mobile-friendly layout for an easy view of sensor inputs and alarms.
No additional software is required for the configuration of the device.
Server Cabinet Temperature and Humidity Monitoring
Remote Equipment Monitoring
F200 Key Features
Simple plug-and-play installation and setup
Web-accessible with a clean, easy to use, mobile-friendly web interface
Monitors eight dry contact inputs and four temperature or temperature/humidity sensors, plus one zone of leak detection
Single zone leak detection supports up to 200’ of leak detection sensing cable and/or spot detectors
USB power – run the F200 from:
The included wall wart
The USB port on a computer plugged into a wall outlet (not an undocked laptop)
A USB hub that provides 500mA of power to the F200 and is powered by an external power supply plugged into a wall outlet
Multiple alarm notification configurations including audible and visible indicators, integrated web interface, email messaging, and SNMP traps
Relay output allows for simple control of an external device upon alarm condition
Modbus output enables simple integration to a Building Management System (BMS)
Integrated logging and trending – trending data available as a downloadable CSV file
Timekeeping via RTC or NTP
Included Equipment: F200 controller; 5V USB (Type A) wall wart power adapter with Type C,G, and I blades; USB mini B to USB A cable
Additional Requirements: Digital temperature sensors, digital temperature/humidity sensors, leak detection leader cable, leak detection sensing cable, SD-Z or SD-Z1 spot detectors, end-of-line terminator, network cable, rack mount kit (as needed for application)
Power: (US) 5VDC @ 500mA max; 110/240VAC 50/60Hz; Wall adapter (Type A blade) to USB connector, with Type C, G, and I blades for international use (included)
Wired Inputs
Temperature/Humidity: 4 1-wire digital temperature or 1-wire digital temperature/humidity sensor inputs; RJ11 connectors; plug-and-play; configurable alarm points
Digital (Dry Contact): 8 digital alarm points; configurable
Sensing Cable: One zone leak detection, compatible with all SeaHawk sensing cables and SD-Z and SD-Z1 spot detectors
Cable Input: Requires 15ft (4.6m) leader cable and EOL terminator (not included), or wire one SD-Z1 directly to the F200
Maximum Sensing Cable Length: 200ft (61m) of sensing cable
Relay Output: 1 Form C summary relay; 2A @ 30VDC, 0.5A @ 125VAC. Configurable as summary alarm output or manual operation.
Alarm Notification
Panel: Audible alarm, visible LED
Integrated Web Interface: Dashboard overview with alarm indicators
Email: Up to 8 email recipients; email sent on alarm to recipients, distribution list, or email-to-SMS
SNMP Traps: Multiple community strings
Relay: 1 Form C summary relay output
Web Interface Login Security: 8 password read only users; 8 password read/write users
Communication Port
Ethernet: 10/100 BaseT, RJ45 connector; 500 VAC RMS isolation; DHCP capable; Static IP-addressable
Protocols
TCP/IP: ARP; DNS; UDP; DHCP
HTML: Supports multiple simultaneous connections
SMTP (email): SMTP authentication; supports SSLv3 RSA:RC4-128:MD5; up to 8 recipients
Modbus TCP/IP: Modbus Server; TCP/IP transmission protocol
SNMP: V1; V2C MIB-2 compliant; NMS Manageable with Get and Traps: V2C Get, V2C and V1 Traps
Timekeeping: Onboard configurable real-time clock (RTC); Network Time Protocol (NTP) capable (internet access required for NTP)
Logging: Logs 50 most recent alarm and return to normal events with date/time stamp
Trending: Records up to 43,200 points of sensor data. Sample interval set from 10 seconds to 1 day. CSV downloadable.
Operating Environment
Temperature: -13° to 158°F (-25° to 70°C)
Humidity: 5% to 95% RH, non-condensing
Altitude: 15,000ft (4,572m) max.
Storage Environment: -40° to 185°F (-40° to 85°C)
Dimensions: 5.63″W x 1.00″H x 2.63″D (143mmW x 25mmH x 67mmD)
Weight: 10.1 oz. (287g)
Mounting: Standalone; keyholes included for wall mount; rack-mount bracket available
Certifications: CE; ETL listed: conforms to UL 61010-1, EN 61010-1; certified to CSA C22.2 NO. 61010-1; RoHS compliant