Zone Leak Detection Equipment

Water splash on surface

A Zone Leak Detection Controller might be the answer if you need to safeguard a limited region against fluid leakage.

When any conductive fluid comes into contact with an associated RLE sensing cable or spot detector, these low-cost controllers alert you nearly instantaneously.

You can rapidly detect the leak and take action before the leak does any harm in a small place where your sensor cable is plainly visible.

Most RLE Zone Controllers use Form C relay output for external alarm notification. Some Zone Leak Detection Hardware uses open protocols for third-part-systems integration.

 

Zone Leak Detection Controllers

RLE Technologies Seahawk LDRA6 Controller

Six Zone Leak Detection Controller

LDRA6

The LDRA6 is compatible with SeaHawk sensing cables and SeaHawk SD-Z & SD-Z1 spot detectors as a zone leak detection solution. The LDRA6 can detect the presence of water, conductive fluids, and chemicals. The LDRA6 sets off an alert in the appropriate zone when a leak is discovered.

LDRA6 can accommodate up to 1,000 feet (305 meters) of sensing cable or one or more spot detectors in each of the six zones. The Leader Kit (LC-KIT) is required for each zone used as a Leak Detection Input.

Each input has a relay output and the panel has one summary relay output.

The Modbus capabilities of the LDRA6 enable it to communicate with other Modbus-compliant devices.

LDRA6 Key Features

  • Monitor up to 1000 feet (305 meters) of leak detection sensing cable and/or spot detectors per zone; 6000 feet (1830 meters) total,
  • The LDRA6 fully integrates with RLE’s family of leak detection cables.  One controller can monitor an area for both water and chemical leaks with our distinct leak detection cables.
  • Create a unique combination of zone leak detection and dry contact alarm annunciation
  • Adjustable leak thresholds fine-tune the system
  • Supervised inputs monitor cable for breaks and contamination
  • Form C relay output for each input enables communication with BMS/NMS/BAS via Modbus RTU (EIA-485)
  • One tri-color notification LED per input and one audible alarm

LDRA6 Specifications

Included Equipment: LDRA6 alarm panel

Additional Requirements: Isolated RLE power supply, leader cable, end-of-line (EOL) terminator, sensing cable (as needed for application)

LDRA6 Power: Requires an isolated power supply.

LDRA6 Inputs

  • Leak Detection Cable: Compatible with SeaHawk sensing cable and SD-Z and SD-Z1 spot detectors (not included)
  • Cable Input: Requires 15ft (4.6m) leader cable and EOL terminator for each zone (not included)
  • Maximum Length: 1000 feet (305m) of leak detection sensing cable and/or spot detectors per zone; 6000 feet (1830m) total
  • Detection Response Time: When used with conductive fluid sensing cable or chemical sensing cable, 20-3600sec, software adjustable in 10-second increments; ±2sec

LDRA6 Outputs

  • Relay: 1 Form C Summary Alarm Relay, 6 Form C alarms, one per input/zone 1A @ 24VDC, 0.5A resistive @ 120VAC; Configurable for supervised or non-supervised, latched or non-latched

Communication Ports

  • EIA-232: 9600 baud; Parity none; 8 data bits, 1 stop bit
  • EIA-485: 1200, 2400, 9600 or 19,200 baud; Parity none, odd, even (programmable); 8 data bits, 1 stop bit

Protocols

  • Terminal Emulation (EIA-232): VT100 compatible
  • Modbus (EIA-485): Server; RTU Mode; Supports function codes 03, 04, 06, and 16

Alarm Notification

  • Audible Alarm: 85DBA @ 2ft (0.6m); re-sound (disabled, 8,16 or 24 hours)
  • Visible Alarm: LED: Alarm: red; Cable Fault: yellow

Front Panel Interface

  • LED Indicators: Power: 1 green (on/off); 1 tri-color Status LED per zone (6 total) (Power On: green; Alarm: red; Cable Fault: yellow)
  • Push Buttons: Quiet/Test/Reset: 1

Download the LDRA6 Data Sheet for more detailed information. 

Contact FMS Integration for more details on your application.

Three Zone Leak Detection Controller

BMS-LD3Z

The BMS-LD3Z is compatible with SeaHawk sensing cables and SeaHawk SD-Z & SD-Z1 spot detectors as a zone leak detection solution. The BMS-LD3Z can detect the presence of water, conductive fluids, and chemicals. The BMS-LD3Z is designed for integration with Building Management Systems using Modbus-RTU or BACnet MS/TP.

A supervised system, the controller continuously monitors the cable for leaks, breaks, and disconnects and sends an alarm notification when one is detected.

BMS-LD3Z can accommodate up to 1,000 feet (305 meters) of sensing cable or one or more spot detectors in each of the six zones. The Leader Kit (LC-KIT) is required for each zone used as a Leak Detection Input.

BMS-LD3Z Specifications

Power: Hardwired 24VDC, 500mA, or RLE power supply PSWA-DC-24-ST (optional; not included)

Included Equipment: BMS-LD3Z, DIN rail mount adapter

Required Accessories: One LC-KIT per zone of leak detection; SC, SC-ZH, SC-C, or SD-Z.

Sensing Cable: Compatible with all RLE sensing cables and the SD-Z and SD-Z1 spot detectors.

  • Cable Input: Three cable inputs; EACH input requires LC-KIT: 15ft (4.57m) leader cable and EOL (not included)

  • Maximum Length: Up to 1,000ft (305m) of sensing cable and spot detectors per zone; 3,000ft (915m) total

  • Detection Response Time: < 10 seconds

  • Cable Break Detection: Yes

Communications Ports

  • EIA-232: USB Connector; 115200 Baud, 8 data bits, no parity, 1 stop bit

  • EIA-485: 9600, 19200, 38400 or 76800 baud (selectable); Parity: None, 8 data bits 1 stop bit

Protocols

  • Modbus RTU (EIA-485): Server RTU mode supports function codes 03 and 04

  • BACnet MS/TP (EIA-485)

External Interface

  • Push Button: Factory reset

  • LED Indicators: Power/Status – 1 tricolor; Leak Zone Status- 1 tricolor

  • DIP Switches: SW 1 – Device configuration; SW 2 – Modbus/BACnet device ID

Operating Environment

  • Temperature: 32°F to 122°F (0°C to 50°C)

  • Humidity: 5% to 95% RH, non-condensing

Dimensions: 5.25”W x 6.0”H x 1.75”D (133mmW x 152mmH x 44.5mmD)

Weight: 8.0 oz. (228g)

RLE SeaHawk LD1000 Leak Detection Controller

Single Zone Leak Detection Controller

LD1000

Up to 1,000 feet (305 meters) of sensor cable can be monitored by the SeaHawk LD1000 single-zone water leak detection controller. All SeaHawk sensing cables, as well as the SeaHawk SD-Z and SD-Z1 spot detectors, are compatible.

The LD1000 is a standalone leak detection controller with an audio alert and three LED indications. It’s perfect for tiny spaces where the sensing cable or spot detector is accessible, leak areas are apparent, and situations where the audible/visual warning may be heard. Furthermore, all LD1000 devices are Modbus capable, allowing them to be integrated into existing monitoring systems through Modbus output.

LD1000 Key Features

  • Monitors up to 1,000 feet (305 meters) of leak detection sensing cable and/or spot detectors

  • Three LED indicators: Power, Leak, Fault

  • Modbus output for BMS integration (all units purchased after 3/1/2019)

  • Selectable audible alarm annunciation

  • Configurable for supervised or non-supervised operation

  • Adjustable sensitivity settings

  • Wall mount enclosure

  • Two Form C output relays for leak and fault alarms

LD1000 Specifications

Included Equipment: LD1000 controller, leader cable, end-of-line (EOL) terminator

Additional Requirements: RLE power supply, sensing cable, and spot detector (as needed for application)

Power: Requires an isolated power supply for DC operation.

  • 24VDC (±10%) Isolated @ 300mA max.; requires RLE power supply PSWA-DC-24-ST (not included)

  • 24VAC (±10%) @ 300mA max.; requires RLE power supply WA-AC-24-ST (not included)

Inputs

  • Leak Detection Cable: Compatible with SeaHawk sensing cables (not included)

  • Cable Input: Requires 15ft (4.6m) leader cable and EOL terminator (included)

  • Maximum Sensing Cable Length: 1,000 feet (305m) of sensing cable

  • Detection Response Time: Configurable for 10sec or 2min, ±10%, when used with conductive fluid or chemical sensing cables.

Relay Outputs: 1 Form C Leak Relay, 1 Form C Cable Fault Relay, configurable to 2 Summary Alarm Relays; 1A @ 24VDC, 0.5A resistive @ 120VAC; configurable for supervised or non-supervised, latched or non-latched

Communications Port

  • EIA-485: 9600 or 19,200 baud; Parity none; 8 data bits, 1 stop bit

Protocols

  • Modbus (EIA-485): Server; RTU Mode; Supports function codes 03, 04, and 06

Alarm Notification: Audible Alarm 85DBA @ 2ft (0.6m); Selectable

Front Panel Interface

  • LED Indicators: Power: 1 green (on/off); Cable Fault: 1 amber; Leak Detected: 1 red

  • Push Buttons: 1: Quiet, Reset, Test

Operating Environment

  • Temperature: 32° to 122°F (0° to 50°C)

  • Humidity: 5% to 95% RH, non-condensing

  • Altitude: 15,000ft (4,572m) max.

Storage Environment: -4° to 158°F (-20° to 70°C)

Dimensions: 4.125″W x 5.5″H x 2.25″D (105mmW x 140mmH x 58mmD)

Weight: 27.0 oz. (765g)

Mounting: Wall mount

RLE SeaHawk LD310 Leak Detection Controller

One Zone Leak Detection Controller

LD310

Up to 300 feet (91 meters) of sensor cable can be monitored by the SeaHawk LD310 single-zone water leak detection controller. All SeaHawk sensing cables, as well as the SeaHawk SD-Z and SD-Z1 spot detectors, are compatible.

The LD310 is a standalone leak detection controller with an audio alert, and three LED indications. It’s perfect for tiny spaces where the sensing cable or spot detector is accessible, leak areas are apparent, and situations where the audible/visual warning may be heard. Relay outputs for system integration to external monitoring systems.

LD310 Key Features

  • Accommodates up to 300 feet (91 meters) of sensing cable and/or spot detectors, or

  • Visible alarm indicator

  • Two Form C output relays for leak and fault alarms

  • Audible and visible alarm notification

  • Adjustable leak alarm sensitivity thresholds

  • Configurable for supervised or non-supervised operation

  • Distinguishes normal conditions from alarm conditions

  • Quickly returns to normal

LD310 Specifications

Included Equipment: LD310 controller, leader cable, end-of-line (EOL) terminator

Additional Requirements: Power supply WA-DC-5-ST, sensing cable and spot detector (as needed for application)

Power: Requires an isolated power supply.

  • 5VDC Isolated (±10%) @ 100mA max; requires RLE power supply WA-DC-5-ST (not included)

Inputs

  • Leak Detection Cable: Compatible with all SeaHawk sensing cables as well as SD-Z and SD-Z1 spot detectors (not included)

  • One Cable Input: Requires 15ft (4.6m) leader cable and EOL terminator (included)

  • Maximum Sensing Cable Length: 300ft (91m) of sensing cable

  • Detection Response Time:  When used with sensing cables, less than 20sec; 10sec typical.

Outputs: 2 Form C Alarm Relays (leak and fault); 1A @ 24VDC, 0.5A resistive @ 120VAC; configurable as supervised or non-supervised

Alarm Notification

  • Audible Alarm: 85dB @ 10cm (min)

  • Visual Alarm: Bi-color LED

Front Panel Interface

  • Audible Alarm: Indicates cable break or leak detected

  • LED Indicator:

    • Normal Operation: Green

    • Cable Fault: Flashing orange

    • Leak Detected: Flashing red

  • Push Button Switch:

    • Push Once: Silence alarm

    • Push and Hold for 5 Seconds: Initiates system test, resets system, clears all active alarms

Operating Environment

  • Temperature: 32° to 122°F (0° to 50°C)

  • Humidity: 5% to 95% RH, non-condensing

  • Altitude: 15,000ft (4,572m) max.

Storage Environment: -4° to 158°F (-20° to 70°C)

Dimensions: 4.4”L x 2.5”W x 1.5”H (11.2cmL x 6.4cmW x 3.8cmH)

Weight: 0.2lb (0.10kg)

RLE WiNG-LD Wireless Zone Leak Detection Sensor

Wireless Leak Detection Sensor

WiNG-LD

WiNG leak detection sensors are a great addition to the WiNG wireless sensor technology product line. The WiNG-LD Leak Detection technology safeguards your facility against water and chemical spills. The WiNG-LD wireless sensor may be used in conjunction with an SD-Z or SD-Z1 spot detector or RLE leak detection sensing cables.

Small form factor and long battery life

WiNG sensors are small and inconspicuous, but they have an industry-leading battery life — at room temperature, sensor batteries may last up to 12 years. WiNG sensors keep this longer battery life by sending measurements to the WiNG-MGR web interface every 10-20 seconds.

 

Long transmission distance

 

The WiNG system offers an unrivaled transmission range between sensors and manager: up to 100 feet through several walls, 270 feet through one wall, and 600 feet indoors with a direct line of sight. While this range is more than enough for most applications, some signals must be pushed through more complicated physical or noisy RF environments. In these cases, the WiNG-RXT range extender may be used to increase the application’s transmission distance by up to 1,000 feet of the direct line of sight.

Available Wireless Leak Sensor Configurations

  • WiNG-LD-LC : WiNG Leak detector for use with sensing cable; 900MHz wireless transmitter; includes LC-Kit; requires SC, SC-R, SC-ZH or SD-Z

  • WiNG-LD-LC-868 : WiNG Leak detector for use with sensing cable; 868MHz wireless transmitter; includes LC-Kit; requires SC, SC-R, SC-ZH or SD-Z

  • WiNG-LD-M : WiNG Leak detector for use with chemical sensing cable; 900MHz wireless transmitter; includes LC-Kit-M; requires SC-C

  • WiNG-LD-M-868 : WiNG Leak detector for use with chemical sensing cable; 868MHz wireless transmitter; includes LC-Kit-M; requires SC-C

  • WiNG-LD-SPOT : WiNG Leak detector for use with spot detector; 900MHz wireless transmitter; includes SD-Z1

  • WiNG-LD-SPOT-868 : WiNG Leak detector for use with spot detector; 868MHz wireless transmitter; includes SD-Z1

Key Features

  • Proprietary wireless design

  • Monitor for leaks with one of the following configurations:

    • One SD-Z1 spot detector

    • One SD-Z spot detector and up to an additional 50 feet (15m) of leak detection sensing cable

    • Up to 100 feet (30.5m) of leak detection sensing cable

  • Available in 868MHz and 900MHz configurations

  • A transmission range between manager and sensors that is second to none:

    • Up to 100 feet (30.5m) through multiple walls

    • Up to 270 feet (82.3m) through one wall

    • Up to 600 feet (183m) direct line of sight

    • Add up to 1,000 feet (305m) direct line of sight with a WiNG-RXT range extender

  • Unparalleled sensor battery life:

    • Up to 5 years across full operating range: -13°F to 185°F (-25°C to 85°C)

    • Up 8 years at temperatures up to 122°F (50°C)

    • Up to 12 year battery life at room temperature

  • Support 250 sensors on a single manager, up to 400 sensors with range extenders

  • Polling rate of 10-20 seconds

WiNG-LD Specifications

Power: 3.6V AA lithium battery

Battery Life

  • Up to 5 years when system spans full operating temperature range.

  • Up to 8 years at room temperatures up to 122°F (50°C)

  • Up to 12 years at room temperature

Shelf Life: 10 years in quiescent mode with battery installed

Transmission

  • Interval: 10-20 seconds (random)

  • Frequency: Available in 868MHz and 900MHz configurations

  • Range: Up to 600ft line of sight

Leak Detection Input: Accepts up to 100ft (30.5m) of sensing cable, 50ft (15m) of sensing cable and one SD-Z spot detector, or 1 SD-Z1 spot detector.

  • Compatibility: Compatible with all RLE sensing cables and the SD-Z and SD-Z1 spot detectors.

  • Sensor Response Time: < 20 seconds

  • Cable Break Detection: Yes

  • Cable Sensitivity: Configurable

Operating Environment

  • Temperature: -13ºF to 185ºF (-25ºC – 85ºC)

  • Humidity: 0% to 90% RH (Non-condensing)

  • Altitude: -200 ft to 15,000 ft (-70m to 4572m)

Mounting: Free standing, zip ties, screw and keyhole – spaced 2.5” (6.4cm), junction box – 2 screws spaced 3.28” (8.3cm)

Dimensions and Weight: 4.4”L x 2.5”W x 1.5”H (11.2cmL x 6.4cmW x 3.8cmH), 0.2lb (0.10kg)

Certifications and Standards: CE UL61010, CSA 22.2 #61010, IEC 61326-1, FCC 47CFR 15B, IC ICES-003, EN 61000-3-2, EN61000-3-3, ETSI EN 301 489-1, ETSI EN 301 489-3; FCC ID: X7J-A11072401: IC: 8975A-A11072401