Distance-Read Leak Detection Equipment provides the best features when looking for pinpoint accuracy with your data center application.

Most common is the Water Leak Detection applications, whether under a raised floor, piping, or other hard-to-see areas. Server Rooms and Data Centers benefit well from this Leak Detection technology.

Distance-read panels can display a distance marker, then personnel can cross-reference to a Leak Detection Reference Map. A more advanced system can show a leak marker on an image, and take the guesswork out of where to look.

All Distance-Read Controllers support system integration using open protocols. Some models also use Form C relay output.

 

Server Room Raised Floor Tile Being lifted

Server Room Leak Detection Controllers

RLE Technologies Seahawk LD5200 Distance Read Controller

LD5200 Distance-Read Controller

The Goliath of Leak Detection Controllers

Any disaster mitigation strategy must include measures to protect a facility from hazardous leaks. The LD5200 combines advanced leak-detecting technology with a user-friendly UI. This integration enables customers to set up a distance-read leak detection system that monitors up to 10,000 feet of sensing cable and successfully safeguards precious assets fast and easily.

Configuration And Monitoring Via LCD Or Web Interface

The LD5200 is a device that RLE Technologies created with the end-user in mind. The LCD touch screen provides access to all essential device functions, including the ability to set up, monitor, find, and acknowledge leaks. The LD5200 may be utilized as a stand-alone device.

While the LD5200 Panel has a robust independent operation, it also offers extensive integration options. The LD5200 can provide leak detection and warn for an entire building through a single IP address. The LD5200’s multiple communications ports enable it to serve as an aggregation device for a number of secondary leak detection devices. The LD5200 also works with BMS, EPMS, DCiM, and NMS platforms.

LD5200 Key Features

  • Monitors up to 10,000 feet of sensing cable

  • Stand-alone or integrated leak detection and notification

  • Annunciates multiple, simultaneous leaks when other RLE distance-read controllers are integrated into the system

  • Pinpoints leaks quickly and accurately

  • Aggregates data from up to 127 RLE leak detection controllers – manage an entire building’s leak detection through one IP address

  • Configure up to 32 virtual zones

  • Sends direct email alarm notification

  • Access the device remotely via the robust web interface – any time, any place

  • Create up to 10 interactive leak detection reference maps

  • Logs a wide variety of events and alarms

  • Detailed alarm history with time and date stamp assists in troubleshooting

LD5200 Specifications

Included Equipment: LD5200 controller with power supply, leader cable, end-of-line (EOL) terminator

Additional Requirements: Sensing cable (as needed for application)

Power: Requires a dedicated circuit within close proximity, marked as the disconnecting device for the LD5200. 

  • 100-240VAC@ 500mA max, 50/60Hz power supply; dedicated circuit required

Sensing Cable Input – Compatible with all SeaHawk sensing cables (not included)

  • Cable Input: Requires 15ft (4.6m) leader cable and EOL (included)

  • Maximum Sensing Cable Length: 10,000ft (3,048m) of sensing cable

  • Minimum Sensing Cable Length: 35ft (11m)

  • Detection Accuracy: ± 2ft (0.6m) +/- 0.5% of the cable length

  • Detection Repeatability: ± 2ft (0.6m) +/- 0.25% of the cable length

  • Detection Response Time: 5-990 seconds, software adjustable in 5 second increments; ±2 seconds

Outputs

  • Analog: 4-20mA Loop Powered, 18-36VDC, RL = 500 Ohm max.

  • Relay: 1 DPDT Leak Relay, 1 DPDT Cable Break Relay (allows each alarm to be sent to two places); 1A @ 24VDC, 0.5A resistive @ 120VAC; configurable for supervised or non-supervised, latched or non-latched

  • Maintenance Relay: 1A @ 24VDC, 0.5A resistive @ 120VAC; configurable for supervised or non-supervised, latched or non-latched

Communication Ports

  • EIA-485 (Port 1, Port 2, Port 3): 9600, 19200, or 38400 baud (selectable); No parity, 8 data bits, 1 stop bit

  • EIA-232: 9600 baud; No parity, 8 data bits, 1 stop bit

  • RJ-45: 10/100BaseT Ethernet port (TCP/IP)

Protocols

  • EIA-485: Modbus RTU Client & Server; BACnet MS/TP; N2

  • EIA-232: Terminal emulation, VT100 compatible

  • RJ-45: Ethernet: TCP/IP; Modbus/TCP/UDP, Client & Server; SNMP V1, V2, V3, NTP, SMTP, DNS; BACnet/IP

Alarm Notification

  • Audible Alarm: 85DBA @ 2ft (0.6m); re-sound 0-999min

  • Visible Alarm: Alarm indicated on LCD touch screen and through a web interface

Logging Capabilities – Logs are downloadable to .txt file

  • Alarm History/Event Log: Last 1,024 events

  • Trend Log: Cable current level once per day, for the last 365 days

Login Security

  • LCD Touch Screen: No password is required to view controller status and data. Administrator password limits access to configuration options.

  • Web Interface: Username and password can be configured

Front Panel Interface

  • Display: 480 x 272 pixel color backlit LCD touch screen; 95.04mm x 53.85mm

Operating Environment

  • Temperature: 32° to 122°F (0° to 50°C)

  • Humidity: 5% to 95% RH, non-condensing

  • Altitude: 15,000ft (4,572m) max.

Storage Environment: -4° to 158°F (-20° to 70°C)

Enclosure

  • NEMA Type 1

  • Dimensions: 12.5″W x 10″H x 3.25″D (318mmW x 254mmH x 83mmD)

  • Weight: 8.2 lbs. (3.7kg)

  • Mounting: Wall mount

Certifications: CE; ETL listed: conforms to UL 61010-1, EN 61010, CSA C22.2 No. 61010-1, IEC 61326:1997; RoHS compliant

LD2100 Distance-read controller

LD2100 Distance-Read Controller

The Best Bang for your Buck for Distance-Read Controllers

The LD2100 is a distance-read controller that works with 5,000 Feet of RLE leak detection cable. LD2100 is designed to monitor ample facilities and sophisticated leak detection applications. Large leak detection applications with raised floors, museums, libraries, data centers, clean rooms, communications centers, and other vital places benefit from the LD2100.

Web Interface, Interactive Map and Open Protocols

An email notification alert will be immediately sent when a leak is detected. The LD2100 includes a user-configurable map that will graphically identify the position of the leak on the map. Open Protocols such as Modbus, BACnet, and SNMP allow for easy integration to Building Monitoring Systems and other third-party-based solutions.

LD2100 for Retrofit Applications

This powerful controller works excellent for retrofitting older leak detection systems. The small form factor makes it possible to install into older LD2500, LD5000, and LD5100 water leak detection panels.

LD2100 Product Features

  • Monitors up to 5,000 feet (1,524 meters) of sensing cable and/or spot detectors
  • Interactive web-based leak detection map – avoid costly damage and downtime with fast leak notification
  • Adjustable leak, delay, and contamination thresholds
  • Identify cable disconnects & breaks
  • Thirty-two configurable zones allow users to label unique areas for quick identification
  • SNMP, Modbus, BACnet, and summary relay output allows for simple integration with BMS, NMS, & BAS
  • SMTP (email) notification of alarm conditions
  • Audible alarm
  • No factory calibration required
  • Annunciate multiple, simultaneous, leaks when other distance-read controllers are integrated into the system

LD2100 Specifications

Included Equipment: LD2100 controller, leader cable, end-of-line (EOL) terminator

Additional Requirements: Isolated RLE power supply, sensing cable (as needed for application), network cable

Power: Requires an isolated power supply.

  • 24VDC Isolated @ 600mA max., 50/60Hz; requires RLE power supply PSWA-DC-24 (not included)
  • 100/120/230-240VAC @ 500mA max., 50/60Hz; requires RLE LD-ENC enclosure (not included)

Output: 1 Form C summary relay, 1A @ 24VDC, 0.5A resistive @ 120VAC; configurable for latched or non-latched

Inputs

  • Leak Detection Cable: Compatible with SeaHawk sensing cable (not included)
  • Cable Input: Requires 15ft (4.6m) leader cable and EOL terminator (included)
  • Maximum Length: 5,000ft (1524m) of leak detection sensing cable
  • Minimum Length: 35ft (11m)
  • Detection Accuracy: ± 2ft (0.6m) +/- 0.5% of the cable length
  • Detection Repeatability: ± 2ft (0.6m) +/- 0.25% of the cable length
  • Detection Response Time: When used with sensing cable, 5-995sec; software adjustable in 5 second increments; ±2sec.

Communication Ports

  • EIA-485: 9600, 19200, 38400, or 56700 baud (selectable); Parity: none, even or odd, 8 data bits, 1 stop bit
  • EIA-232: DB9 female connector; 9600 baud; 8 data bits, no parity, 1 stop bit
  • Ethernet: 10/100BaseT Ethernet port; 500VAC RMS isolation

Protocols

  • EIA-485: Modbus RTU, Client & Server; BACnet MS/TP; N2
  • EIA-232: Terminal emulation, VT100 compatible
  • Ethernet: Ethernet, TCP/IP; Modbus/TCP/UDP, Client & Server; SNMP V1, V2, V3, NTP, SMTP, DNS; BACnet/IP

Alarm Notification

  • Visible Alarm: Green, alphanumeric, dot matrix LED display; bi-color status LED
  • Audible Alarm: 70dBA @ 2ft (0.6m); re-sound configurable (disabled, 0-24 hours)
  • Email (Ethernet): 4 email recipients; email sent on Alarm and Return to Normal; each alarm notifies all email recipients
  • SNMP Traps (Ethernet): 4 Community Strings

Logging Capabilities

  • Event Log: Last 500 events
  • Trend Log: Cable current level once daily for the last 288 days

Login Security

  • Web Browser Access (Ethernet): Web password Read-Only; 1 Web password Read/Write
  • Terminal Emulation Access: None

Front Panel Interface

  • Display: Green alphanumeric dot matrix display
  • Push Buttons: Test/Reset: 1
  • LED Indicators: Power/Status: 1 bi-color (Power On: green; Alarm: red)

Operating Environment

  • Temperature: 32° to 122°F (0° to 50°C)
  • Humidity: 5% to 95% RH, non-condensing
  • Altitude: 15,000ft (4,572m) max.

Storage Environment: -4° to 185°F (-20° to 85°C)

Dimensions & Weight: 8″W x 4.25″H x 1.25″D (203mmW x 108mmH x 32mmD); 1.5 lbs. (680g)

RLE SeaHawk LD1500 Distance-Read Controller

LD1500 Distance-Read Controller

Perfect Distance-Read Controller for System Integration

The LD1500 is a distance-read controller that works with 1500 Feet of RLE leak detection cable and/or spot detectors. LD1500 is designed to monitor hard-to-see areas. Server Room and Data Center applications with raised floors, museums, libraries, data centers, clean rooms, communications centers, and other vital places benefit from the LD1500.

Open Protocols for Easy System Integration

This distance-read controller supports Open Protocols such as Modbus, BACnet, Johnson Controls N2, and SNMP allowing for easy integration to Building Monitoring Systems and other third-party-based solutions. The LD1500 is designed to communicate to RLE SeaHawk LD5200 and LD2100 as a slave module. Easy plug-n-play to other RLE Controllers saving configuration time.

LD1500 Panel Features

  • Monitors up to 1,500 feet (457 meters) of sensing cable and/or spot detectors
  • Web-based interface – view alarms and configuration with a Web browser
  • Adjustable leak, delay, & alarm sensitivity threshold
  • Modbus integration with LD5200 & LD2100
  • SNMP, Modbus, and BACnet communications
  • The supervised system identifies cable breaks and contamination

LD1500 Specifications

Included Equipment: LD1500 controller, leader cable, end-of-line (EOL) terminator

Additional Requirements: Isolated RLE power supply, sensing cable and spot detector (as needed for application), network cable

Power: Requires an isolated power supply.

  • 24VDC Isolated @ 600mA max., 50/60Hz; requires RLE power supply PSWA-DC-24 (not included)
  • 100/120/230-240VAC@ 500mA max., 50/60Hz; requires RLE LD-ENC enclosure (not included)

Inputs

  • Leak Detection Cable: Compatible with all SeaHawk sensing cables (not included)
  • Cable Input: Requires 15ft (4.6m) leader cable and EOL terminator (included)
  • Maximum Length: 1,500ft (457m) of sensing cable
  • Minimum Length: 35ft (11 m)
  • Detection Accuracy: ± 2ft (0.6m) +/- 0.5% of the cable length
  • Detection Repeatability: ± 2ft (0.6m) +/- 0.25% of the cable length
  • Detection Response Time: When used with sensing cable, 5-995sec; software adjustable in 5 second increments; ±2sec.

Communication Ports

  • EIA-485: 1200, 2400, 9600, 19200, or 38400 baud (selectable); Parity: none, even or odd, 8 data bits, 1 stop bit
  • EIA-232: DB9 female connector; 9600 baud; 8 data bits, no parity, 1 stop bit
  • RJ-45: 10/100BASE-T Ethernet port; 500VAC RMS isolation

Protocols

  • EIA-485: Modbus RTU, Server; BACnet MS/TP; N2
  • EIA-232: Terminal emulation, VT100 compatible
  • RJ-45: Ethernet, TCP/IP; Modbus TCP/UDP, Server; SNMP V1, V2; NTP, SMTP, DNS; BACnet/IP

Alarm Notification

  • Visual Alarm: Bi-color status LED
  • SNMP Traps/Informs (Ethernet): 2 Community Strings

Logging Capabilities

  • Event Log: Last 10 events

Login Security

  • Web Browser Access (Ethernet): 1 Web password Read-Only; 1 Web password Read/Write
  • Terminal Emulation Access: None

Front Panel Interface

  • LED Indicators: Power/Status: 1 bi-color (Power On: green; Alarm / Cable Fault / Cable Contamination: red)

Operating Environment

  • Temperature: 32° to 122°F (0° to 50°C)
  • Humidity: 5% to 95% RH, non-condensing
  • Altitude: 15,000ft (4,572m) max.

Storage Environment: -4° to 185°F (-20° to 85°C)

Dimensions: 7″W x 3.62″H x 1.25″D (178mmW x 92mmH x 32mmD)

Weight: 1.5 lbs. (680g)